Index >> Products >> Monitoring >> Poseidon xxxx
Poseidon 3268: termometru WEB & I/O cu SNMP
Monitorizare Ethernet temperatura / umiditate cu 2 iesiri cu relee si 4 intrari de contact fara potential (Web, SNMP, si E-mail). Releele de iesire pot fi controlate prin Web.
Note: Shorted version - full details in english version.
| Poseidon 3268 este un dispozitiv IP unic care ofera 2 iesiri cu relee (NO/NC). Poseidon 3268 masoara temperatura si umiditatea, si monitorizeaza patru intrari de contact fara potential.
Intrarile digitale (pentru contacte fara potential) pot fi folosite pentru a conecta contacte de usi, detectoare de fum, detectoare de inundatie, sau detectoare de absenta a tensiunii de retea de 110/230V CA.
Releele de iesire pot controla incalzirea / racirea cofretelor folosind o sonda locala (functie “termostat” / “higrostat”).
Iesirile pot fi controlate la distanta prin IP (restartare server folosind un dispozitiv PowerEgg, sau deschidere usa cofert de la distanta).
Atunci cind o intrare de contact fara potential este inchisa, Poseidon-ul trimite un e-mail sau un SNMP trap. Alarmarea poate fi intirziata cu un timp definit (un e-mail este trimis daca usa cofretului a fost deschisa pentru mai mult de 5 minute).
Folosind software-ul PD Trigger, alarmarile pot fi redirectionate catre SMS sau prelucrate in conformitate cu regulile definite in PD Trigger (inchidere/deschidere releu la distanta prin IP, deschiderea unui mesaj pop-up in Windows). Intr-o aplicatie tipica, Poseidon 3268 controleaza mediul intr-un cofret care este echipat cu un ventilator. Alarmarile privind temperatura critica si deschiderea uii sint trimise catre un sistem central. Poseidon 3268 este deseori folosit pentru restartarea unui server sau a unei surse de alimentare de la distanta. |
|
Caracteristici de baza
- Ethernet: RJ45 (10BASE-T)
- WEB: web server incorporat
- Senzori: 1xRJ11 1-Wire (max. 5 senzori temperatura / umiditate)
- Intrari digitale: 4 intrari digitale (contact fara potential)
(contact usa, detector de fum, detector de tensiune 11/230VAC, detector de scurgeri de apa, detector de nefunctionare ventilator de racire)
- Iesiri digitale: 2 relee (24VCC)
(aer conditionat, alimentare server, sirena / lumina de avertizare)
- Functii incorporate: Controlul iesirii folosind o valoare digitala de intrare sau o valoare masurata de un senzor(mod “termostat” / “higrostat”)
- Alarmari (valoare in afara gamei definite): SNMP trap, E-mail
- Protocoale de comunicatie M2M: SNMP, XML
- Suport pentru programatori: HWg SDK
- Software suportat
>> Poseidon model XXXX - overview of models
Application
>> Poseidon - application examples
>> Application study - Poseidon family
Sensors
1-Wire sensors
- Total bus length max 60 m
- Each sensor has its own SafeRange. When the range is exceeded (alarm), e-mail or SNMP trap is invoked.
DI (Dry contact inputs) for detectors:
DO (Digital Outputs) Relay:
- Power Detector / Control 110/230V AC: PowerEgg
>> More sensors
Topology
- WEB (HTML)
Values and state of sensors are presented on WWW page. The page is automatically reloaded every 5 second. There is a link to Flash Setup from main HTML page, update FirmWare and others
- XML
All sensor's values as well as alarm status information are available in XML files (values.xml) and any application can log it from XML tags - more information
- SNMP
SNMP is protocol for monitoring of telecommunication devices, network infrastructure and related technology. The Poseidon is fully controllable over SNMP (v1, partially v2) - more information
- Alarms
- SNMP Traps
In case of exceeding "Safe Range" the sensor gets to Alarm status. To notify of this a SNMP Trap including alarm status description is sent to configured IP address - more information
- Email
In case of exceeding "Safe Range" the sensor gets to Alarm status. To notify of this a Email including alarm status description is sent to configured email address - more information
>> Poseidon –
communication protocols
HW interface
Overview of all sensors in our assortment: Sensors and accessories.
- Digital Outputs (Relay switch)
2 switching contacts of internal relay (output contact can be used as a NO (Normally Open) or NC(Normally Close))
- Digital Input (Dry Contact input)
4x input to connect contact (door for example) or output from relay (pins labled as NO or
NC)
- 1-Wire Bus - RJ11
A bus for use in IT, designed to connect temperature and humidity sensors over up to 10m
>> Interface for connecting sensors to Poseidon
Technical specification
- Port 1: Ethernet RJ 45 - 10BASE-T / 10 Mbit/s
- Port 2: SENSORS - 1-Wire bus
- Port 3: 4 Dry Contact input for contact connecting
- Port 4: 2 switching outputs of internal relay
- Power supply : 12V SS
- Device setting:
- UDP Config
- Over WEB - graphic Flash setup interface
- Over SNMP
| Port 1 - Ethernet port |
|
| + Interface |
RJ45 (10BASE-T) – 10 Mbit or 10/100 Mbit network
compatible |
| + Supported protocols |
IP: ARP, TCP/IP (HTTP), UDP/IP (SNMP) |
| + SNMP compatibility |
Ver:1.00 compatible, some parts of the ver 2.0 implemented |
| |
| Port 2 - 1-Wire sensor bus |
|
| + Connector |
RJ12 (6 pins - 4 pins used only = RJ11 compatible) |
| + Sensors / distance |
max. 60 m total lenght |
| |
| Port 3 - Dry contact inputs |
|
| + 4 Contact inputs |
Connect it with a contact directly (dry contact). |
| + Isolation |
Galvanic isolated up to 50V DC |
| + Sensor type |
NO or NC contact switch |
| + Max distance |
Up to 30 m |
| |
| Port 4 - Relay switch outputs |
|
| + 2 Digital outputs |
Control via network (Web, XML, SNMP) or signal local alarm |
| + Isolation |
Relay switch up to 50V DC, max DC current 24V/1A, 50V/0.5A |
| + Switch type |
3 pins, can be used as NO or NC contact switch |
| |
| LED Status indicators |
| + POWER |
Green - power
OK |
| + LINK & Activity |
Yellow - Ethernet
connectivity |
| |
| DIP SWITCH configuration |
| + DIP1 - RS--232 Setup mode |
Not used |
| + DIP2 - Security |
ON = Security mode - remote configuration
disabled
OFF = Non-Security mode - remote configuration enabled |
| |
| Physical parameters |
|
| + Voltage requirements |
9 - 15V / 250 mA DC
coaxial power connector (barrel),
GND on the shield |
| + Dimensions |
102 x 76 x 36 [mm] |
| + Weight |
150 g |
Which software to use
- Configuration: UDP Config - IP address configuration
- Event processing: PD Trigger - reacts to events
- Monitoring and logging: HWg-PDMS - Monitoring software with MS Excel reporting
- Simple Visualization: SNMPcap - I/O and sensors
- Visualization: CapTemp - Process monitoring and control
- Other applications: Third-party SNMP software
- For programmers: HWg-SDK contains interface descriptions and examples of using M2M protocols in several programming languages
PD Trigger application example
With the PD Trigger application for Windows, it is possible to receive alarms (SNMP traps) from an unlimited number of Poseidon products and define conditions and actions based on the originating device and the probe name. For example:
- In case of air conditioning failure in server room A, send a SMS to Peter
- In case of alarm in server room B, send e-mail to Tom
- In case of electricity supply failure anywhere, send SMS to Peter and turn on a warning light at the receptionist's desk

>> Software for the Poseidon family
>> How to order product
>> Fill in Online order form
Coduri de comanda
| OID |
Type description |
600 254
|
Poseidon model 3268 (photo) |
600 255
|
Poseidon 3268 Tset (photo)
|
Accesorii
Power adapter
- Accessories for the 1-Wire bus (RJ11)
Poseidon
T-Box [600
040]
Hub for up to 5 probes over 1-Wire bus (5x RJ11), connecting cable 0,1 meter long.
Poseidon
T-Box2 [600
280]
Hub for up to 2 probes over 1-Wire bus (2x RJ11), connecting cable 3 meter long.
- Temp-1Wire (temperature probe)
- Humid-1Wire (humidity probe)
- Accessories for Inputs (Dry Contact)
- Door contact (photo) [600 119]
Magnetic sensor for door opening detection - small, easy to use..
- PowerEgg
Detection of external AC voltage (110 to 230V), configurable AC output(110 to 230V)
- Flood detector (water leak detection with autonomous sirene)
- Gas leak detector (Gas leak detection with autonomous sirene)
- Smoke detector (Smoke and fire detection with autonomous sirene)
- Motion detector
- Accessories for Output (internal relays)
- PowerEgg
Detection of external AC voltage (110 to 230V), configurable AC output(110 to 230V)
Cuvinte cheie
releu web, termostat activat web, SNMP I/O, termometru web, raport MS Excel
contact fara potential, releu snmp, termostat digital, humidity controler umiditate, releu IP, higrometru, camera rack, sistem monitorizare mediu, Nagios, Zenoss, Cacti, HP OpenView |