| Index >> Products >> Monitoring >> Sensors & accessories
Sens-485-UI connect two analog current or voltage inputs to the Poseidon unit throught RS-485 bus. DIN rail mounting, galvanic separated analog signals, both channels can be configured to measure voltage 0..15V or current 0..25mA.
The Sens-485-UI converter communicates via RS-485 using ASCII protocol, which is compatible with Poseidon family products. The converter applies two addresses of two letters (for example „A“/“a“) except the letter „T“ (see manual).
First channel represents the address with capital letter (for example „A“), the second channel represents the address with small letter (for example „a“). Both addresses are assigned simultaneously with the capital letter assigning.
Basic characteristics
- Input: Two independent channels Ch1 and Ch2
- Each channel can measure voltage or current
- Measured variable can be selected via RS-485
- Voltage range: 0 to +15V DC
- Current range: 0 to +25mA
- Output: RS-485
bus
- ASCII protocol, compatible with Poseidon family products
- Output resolution: two decimal positions
- Construction for mounting on DIN bar
- Power supply 8 to 28V DC, galvanic separation from Ch1 and Ch2
Downloads
Technical specifications
- Ch1 and Ch2
inputs
- Current input: 0 to 25 mA
- Voltage input: 0 to 15V
- Transformational accuracy: measurement error< 0.1% from range
- Insulation strength of Ch1 to Ch2 input: 2kV
- Galvanic separation - inputs to RS-485 and power supply: 4kV
- Dimensions: 22.5 x 85 x 70 mm
- Construction for mounting on DIN bar 35 mm
- Protection class: box/terminal board: IP40 / IP10
- Connecting conductor: 0.5 to 2.5mm2
- Operating temperature range: -25 to +70°C
- Power supply voltage : 8 to 28V DC (polarity reversing protection)
- Consumption: <7 mA, during operating 60 mA
- Interface: RS485 / 9600Bd / 8N1
- Up to 31 converters on RS485 line, up to 1200m distance
- No RS-485 line termination
- Address: 25 addresses „A/a“ to „Z/z“ except „T/t“
- Address substitution: special command via RS-485 line
- Type tests
- General type test under CSN EN 770
- EMC under CSN EN 61326-1
- Safety under CSN EN 61010-1
Terminal wiring

| 1(-), 2(U+), 3(I+): |
CH1 - channel 1 input |
| 4(-), 5(U+), 6(I+): |
CH2 - channel 2 input |
| 7(B), 8(A): |
RS485 line |
| 9(-), 10(+): |
power supply 8 to 28V DC |
The converter mounting
The converter is designed for mounting on the DIN bar 35 mm. Push in the top end and use a flat-head screwdriver to unfasten the pawl. Push the low end in the bar direction to lock. To Dismount follow the instruction backwards.
Connecting to Poseidon devices
Sens-485-UI unit can be connected to the Poseidon family devices with RS-485 bus (Industrial Bus). To connect over RJ45 connector and TP cabling, use these scheme.
Communication protocol
The sensors works in request-response mode. Maximum response time on the line is 20ms.
- Communication bus: RS-485
- Range of addresses: “A/a” .. “Z/z” (except „T/t“) (25 addresses)
- Communication: ASCII, see datasheet
- Response time: max. 20 ms to command
- Baudrate: 9600 baud
- Number od data bits: 8
- Parity: no
- Number of stopbits: 1
Detailed description of communication protocol is available in Product list.
Sens-UI Poseidon support
After connecting to Poseidon model 1250 unit, data measured in Sens-UI unit is available on local network or via internet in Your web browser.
The values are accessible via following protocols:
- Modbus/TCP
- SNMP
- XML
- Email warning on value out of safe range
- SNMP trap warning on value out of safe range
Ordering
The sensor samples are already available. Products are on stock in several pieces. The price can be found on the
Pricelist page.
| OID |
Type description |
600 116
|
Sens-485-UI
(photo)
Ch1 measures voltage (0 to 15V), Ch2 measures current (0 to 25mA), communication over RS-485 |
| 600 117 |
Sens-485-UU
(photo)
Ch1 and Ch2 measures voltage (0 to 15V), communication over RS-485 |
| 600 118 |
Sens-485-II
(photo)
Ch1 and Ch2 measures current (0 to 25mA), communication over RS-485 |
Note: Sens-UI, Sens-UU a Sens-II products differ only in configuration. Ordering code 600117 and 600118 are used especially for simplification of supplies for extensive installation.
Special accessories
Poseidon B-Cable reduction [600 044] (details)
Converting of the RS-485 + Power from the RJ45 connector to terminal unit - 4 pins ( A,B,+,- )
- Sensor RJ45 MIDDLE cable [600 233] (details)
About 0.5 meter long cable, connecting 4 pins ( A,B,+,- ) from terminal unit to RJ45 connector. Cable for connection of middle sensors.
- Sensor RJ45 LAST cable [600 234] (details)
About 0.5 meter long cable, connecting 4 pins ( A,B,+,- ) from terminal unit to RJ45 connector. Cable for connection of the last sensor in-line.
Poseidon S-Hub [600 041] (details)
RS-485 bus splitter for 8+1 RJ45 connectors and TP cables. S-Hub can supply power all connected sensor.
-> Pricelist (ordering)